Minutes of pre-bid meeting - Supply, installation, testing and commissioning of FM-200 automatic fire suppression system in the server room of Bank's Office Building at Bhubaneswar. S. No. | Questions raised by firm’s representative | Clarification given by the Bank | 1. | Whether Novec 1230 can be used in place of FM-200? | It has been advised to only go for FM-200 system as per tender specifications. | 2. | Clarification was sought regarding the transaction cost due to typological error. | It has been confirmed that the transaction cost is ₹ 1000/- + GST charges. | 3. | The firm M/s Ceasefire has asked for increasing the capacity of the gas cylinder from 120 L. | It has been confirmed that the size of the gas cylinder shall be as per tender technical specifications i.e. 120 L. | 4. | The firm M/s Firestop Sales & Service has asked for increasing the discharge time of the gas from 10 seconds. | It has been advised that 10 s will be the minimum discharge time as per tender conditions, while the actual time may be set higher as per site conditions and is under Bank’s discretion. | | |