Corrigendum E-Tender No. RBI/Ranchi/Estate/200/22-23/ET/306 A pre-bid meeting for captioned work was held at 11:00 hours on September 19, 2022 at Office Premises of RBI Ranchi in physical mode. 2. (a) List of Bank’s Officials who attended the meeting- Reserve Bank India, Ranchi | Sl. No. | Name | Designation | 1. | Shri Sandip Kumar Baidya | Manager (Tech- Civil) | 2. | Kum. Prity Kumari | JE (Elect.) | (b) List of Representative of Company / Individual / Firm / Contractor Sl. No. | Name | Address | 1. | Vaibhv Vishal | Legrand (Numeric) | 2. | Shivendra Kumar | Prostarm Info System Ltd. | 3. The queries/request, raised by the participants during the meeting vis-à-vis the clarification given the Bank are given below: Sl. No. | Technical Specification para in Tender Document | Bank’s Requirement | Queries/ Request by Legrand (Numeric) | Queries/ Request by Planet Infrastructure Management Pvt. Ltd. | Our Comments | 1 | B. 7.) Module rating | 30 KW or above | 30 KW or below | 20 KW | Please comply the tender specification. | 2 | C. 1.) Nominal Module full load rating KVA | N + 1, 30 KVA + 30 KVA (spare) | N + 1, 30 KVA + 1 Power Module (spare) | - | Please comply the tender specification. | 3 | C. 3.) Cabinet size | Expandable upto minimum 120 KVA / KW in a single server rack cabinet | Expandable upto minimum 80 KVA / KW in a single server rack cabinet | - | Please comply the tender specification. | 4 | C. 6.) Overload rating | 110% for 1 hour, 10 mins. for 125%, 1 min. for 150%, | 10 min. at 115%, 1 min. at 135% | ≦ 125%: 10 minutes; ≦ 150%: 1 minute; >150%: 1 second. | Please comply the tender specification. | The terms and conditions and specifications of the tender document shall continue to remain same. GM(O-i-C) | |